Planned maintenance contracts usually fail in the gap between the scheduled visit and the breakdown nobody priced. This one fixes the checklist for both visits, sets a 48 hour response, and gives the contractor a $300 ceiling to fix small things on the spot instead of booking a second trip.

Create a document with OneCraft4 A4 pages, editable, then download as a PDF

The document, page by page

Every page as it renders and as it prints, with nothing summarised. Read the wording before you reuse it.

Coolant Air Services
18 Trenerry Way, Braeside · 03 9587 4402 · service@coolantair.example · ARC licence AU12885
HVAC maintenance agreement · Ironworks Gym · version 2Page 1 of 4
HVAC maintenance agreement · Ironworks Gym · version 2Page 2 of 4
HVAC maintenance agreement · Ironworks Gym · version 2Page 3 of 4
HVAC maintenance agreement · Ironworks Gym · version 2Page 4 of 4
HVAC maintenance agreement

This agreement is made on 14 October 2026 between Coolant Air Services, of 18 Trenerry Way, Braeside, called the Contractor, and Ironworks Gym, of 402 Nepean Highway, Mentone, called the Client. It covers the planned maintenance of the equipment listed in clause 1.

$520
Fee a year
2
Visits a year
$300
Parts cap
48 hours
Breakdown response
1. The equipment
1.1
What is under this agreement
Two ducted split systems serving the gym floor, rated 20 kilowatts each and installed in 2021, one 7 kilowatt wall unit in the reception, one 5 kilowatt unit in the office, and the two roof mounted exhaust fans over the weights area. Nothing else on site is covered, and an added unit is quoted before it is added. The first visit is a baseline: every unit is inspected and its condition recorded with photographs, and a fault that already exists is reported and quoted separately, because this agreement maintains working equipment rather than repairing a backlog.
2. The visits
2.1
When and what
Two visits a year, in March before the cooling season ends and in September before the heating season ends, booked two weeks ahead and carried out before 8 am or after 8 pm so the gym floor stays open. The checklist below is done on every unit at every visit.
Task
What is done
March
September
Filters
Washed or replaced, dated on the frame
Yes
Yes
Coils
Indoor and outdoor coils cleaned, fins combed
Yes
Yes
Drains
Condensate tray and line flushed and treated
Yes
Yes
Refrigerant
Pressures and superheat logged, leak check
Yes
Yes
Electrical
Contactors, terminals and current draw checked
Yes
Yes
Controls
Thermostat calibration and schedule reviewed
Yes
Yes
Fans and belts
Bearings, balance and mounts on the exhaust fans
No
Yes
Report
Written report with readings, photos and recommendations
Yes
Yes
Task
What is done
March
September
Filters
Washed or replaced, dated on the frame
Yes
Yes
Coils
Indoor and outdoor coils cleaned, fins combed
Yes
Yes
Drains
Condensate tray and line flushed and treated
Yes
Yes
Refrigerant
Pressures and superheat logged, leak check
Yes
Yes
Electrical
Contactors, terminals and current draw checked
Yes
Yes
Controls
Thermostat calibration and schedule reviewed
Yes
Yes
Fans and belts
Bearings, balance and mounts on the exhaust fans
No
Yes
Report
Written report with readings, photos and recommendations
Yes
Yes
Task
What is done
March
September
Filters
Washed or replaced, dated on the frame
Yes
Yes
Coils
Indoor and outdoor coils cleaned, fins combed
Yes
Yes
Drains
Condensate tray and line flushed and treated
Yes
Yes
Refrigerant
Pressures and superheat logged, leak check
Yes
Yes
Electrical
Contactors, terminals and current draw checked
Yes
Yes
Controls
Thermostat calibration and schedule reviewed
Yes
Yes
Fans and belts
Bearings, balance and mounts on the exhaust fans
No
Yes
Report
Written report with readings, photos and recommendations
Yes
Yes
2.2
Filters and refrigerant
Two sets of standard filters a year are included in the fee. A filter outside the standard size is charged at cost. Refrigerant is not included: a system found low is reported, leak tested, and the gas and the repair are quoted before anything is added, because topping up a leaking system without finding the leak is neither legal nor useful. Refrigerant handling is done by a technician holding a current ARC licence.
3. Breakdowns and parts
3.1
Response time
A breakdown reported by phone or email during business hours is attended within 48 hours. Where the gym floor has no cooling and the forecast is 32 degrees or above, it is attended the same day if reported before noon. Attendance is included; the repair itself is charged under clause 3.2.
3.2
The parts cap
The Contractor may fit parts up to $300 in a single visit without asking, so a capacitor or a contactor is replaced on the spot rather than on a second trip. Anything above $300 is quoted and approved in writing first. Labour on a breakdown is charged at $125 an hour in business hours and $190 outside them.
Why the cap sits at $300
It is set high enough to cover the parts that actually fail in a small commercial split system and low enough that nothing significant is spent without the Client knowing. Every part fitted under the cap is listed on the invoice with its price.
4. Fees
4.1
The annual fee
The fee is $520 plus GST a year for the two visits, the standard filters, the reports and the breakdown attendance. It is invoiced after the March visit and payable within 14 days.
Included in the fee
Quantity
Value
Planned maintenance visits
2
$420.00
Standard filter sets
2
$100.00
Annual fee before GST
$520.00
GST at 10 percent
$52.00
Annual fee including GST
$572.00
4.2
What is charged separately
Breakdown labour, parts, refrigerant, non standard filters, duct cleaning, a system replacement and any work on equipment not listed in clause 1. Each is quoted before it is done, except parts under the cap in clause 3.2.
5. Access, standard of work and general
5.1
Access and safety
The Client gives access to the plant on the roof and to the ceiling spaces, and keeps the roof hatch clear. The Contractor works to its own safe work procedures, holds public liability cover of $20 million and workers compensation as required by law, and leaves every access panel closed and every isolator back on before it leaves.
5.2
What maintenance does and does not promise
The services carry the consumer guarantees under the Australian Consumer Law. Planned maintenance extends equipment life and catches faults early; it does not guarantee that a nine year old system never fails. Where a unit fails twice for the same cause within six months, the Contractor reviews it at no charge and recommends repair or replacement in writing.
5.3
Term, ending and whole agreement
This agreement runs for 12 months from 14 October 2026 and continues until either party ends it on 30 days written notice, with any visit already booked still carried out. A party in serious breach has 10 business days to fix it after notice. This agreement is governed by the law of Victoria and replaces the quotation dated 29 September 2026.
For Coolant Air Services
Name
:
Position
:
Date
:
For Ironworks Gym
Name
:
Position
:
Date
:

Section by section

What each section is for, so you can keep the ones you need and drop the rest.

Parties and key terms
Contractor and client, then the annual fee, the visit count, the parts cap and the response time.
1. The equipment
Six units by capacity and location, and the baseline condition record taken on the first visit.
2. The visits
When the two visits happen, the eight task checklist, and the filter and refrigerant rules.
3. Breakdowns and parts
The 48 hour response, the same day heat rule, the $300 cap and the labour rates.
4. Fees
The $520 annual fee itemised to $572 including GST, and what sits outside it.
5. Access, standard of work and general
Roof and ceiling access, safety and cover, the honest limit of maintenance, term and notice.
Signatures
A block for the contractor and one for the client.

Clauses in this document

How to adapt this agreement

For a larger site, replace the equipment clause with an asset register as an annexure and price per unit rather than as a single annual fee, so adding or removing a unit does not need a new contract. For a critical environment such as a server room or a cool room, add a temperature alarm response time in hours, a requirement for after hours attendance, and a spare parts holding clause. For a strata building, move the access clause to name who holds the roof key and add a rule about working over occupied units, and raise the parts cap only if the committee can approve spending between meetings.

Who this is for

A small commercial site with a handful of split systems and no in house facilities team: a gym, a clinic, a cafe, a suburban office. At that scale the risk is not a catastrophic plant failure, it is a filter nobody changed for two years and a condensate line that finally blocked over a long weekend. A two visit programme with a written checklist and a modest parts cap handles almost all of it. A larger site with rooftop packaged units, a building management system or a critical environment needs a longer agreement with an asset register and an alarm response time, and the clause on what maintenance does not promise is worth keeping in either version.

What makes this document work

The checklist is the scope

Eight tasks run from filters and coils to bearings on the exhaust fans, each marked yes or no for March and September. A client comparing two maintenance quotes can line the checklists up instead of comparing two prices.

A $300 cap turns two visits into one

Clause 3.2 lets the contractor fit parts up to $300 without asking, so a failed capacitor or contactor is replaced on the spot. Every part fitted under the cap is listed on the invoice with its price, and anything above needs written approval.

Refrigerant is not quietly topped up

Clause 2.2 excludes gas from the fee, requires a leak test before anything is added, and says the repair is quoted first, because topping up a leaking system without finding the leak is neither legal nor useful.

Questions people ask

What should an HVAC maintenance agreement include?

The exact equipment covered, how many visits a year and what is done at each, which consumables are included, a breakdown response time, how parts and labour are charged, the annual fee, and what is specifically outside the agreement. All of those are clauses here.

How often should commercial air conditioning be serviced?

Twice a year for a small commercial split system suits most sites, timed before each season rather than at a fixed calendar date. This agreement books March and September, before the cooling and heating seasons end, and runs the visits outside trading hours.

Is refrigerant included in a maintenance contract?

Rarely, and it should not be. Clause 2.2 excludes it, requires a leak test when a system is found low, and has the gas and the repair quoted before anything is added. Refrigerant handling is done by a technician holding a current licence for it.

What is a parts cap?

A dollar limit the contractor can spend on a single visit without stopping to ask. Here it is $300, set high enough to cover the parts that actually fail in a small split system and low enough that nothing significant is spent without the client knowing.

What response time is reasonable for a breakdown?

Forty eight hours in business hours suits a site that is uncomfortable rather than closed. This agreement adds a same day rule when the gym floor has no cooling and the forecast is 32 degrees or above, which is when the difference actually matters.

What is not covered by a maintenance fee?

Breakdown labour, parts, refrigerant, non standard filters, duct cleaning, a system replacement and any equipment not listed in clause 1. Each is quoted before it is done, with the single exception of parts under the $300 cap, which are fitted on the spot and itemised.

Build your own in about a minute

The button below opens the generator with this use case already described. Change the wording to match your own, generate, then edit anything you like.

Make my hvac maintenance agreement with a visit checklist and a parts cap